Rapport I.5. Essais d'un échangeur à tubes ailetés pour réfrigérants secs

Fiche du document

Auteur
Date

1980

Discipline
Type de document
Périmètre
Langue
Identifiant
Collection

Persée

Organisation

MESR

Licence

Copyright PERSEE 2003-2023. Works reproduced on the PERSEE website are protected by the general rules of the Code of Intellectual Property. For strictly private, scientific or teaching purposes excluding all commercial use, reproduction and communication to the public of this document is permitted on condition that its origin and copyright are clearly mentionned.

Résumé En Fr

Finned-tube heat exchanger for dry cooling tower. The most commonly used exchange surface for dry cooling towers is a finned-tube heat exchanger with compact equilateral meshing. The experimental determination of the laws of exchange and load loss on the air side of this type of tube bundle was undertaken for the range of speeds covering all foreseeable uses. Expressed in non-dimensional units, the exchange law has a continuous profile over the whole range studied. The load loss coefficient declines when the Reynolds index rises and the slope declines for a frontal speed of the order of 2 metres per second.

La surface d'échange la plus répandue pour les réfrigérants secs est un échangeur à tubes ailetés à maillage équilatéral compact. Une détermination expérimentale des lois d'échange et de perte de charge côté air de ce type de faisceau a été réalisée pour une gamme de vitesse qui recouvre toutes les utilisations envisageables . Exprimée en nombres adimensionnels, la loi d'échange a une allure continue dans tout le domaine étudié. Le coefficient de perte de charge décroît lorsque le nombre de Reynolds augmente et on observe une diminution de la pente pour une vitesse frontale de l'ordre de 2 m/s.

document thumbnail

Par les mêmes auteurs

Sur les mêmes sujets

Sur les mêmes disciplines

Exporter en